Cold Room Equipment Selection Tool
Enter dimensions and temperature to estimate load and match the right refrigeration unit, panels and door.
Enter Your Requirements
Estimated Configuration
Room volume72 m³
Surface area (6 faces)108 m²
Base refrigeration load5.04 kW
Design load (×1.15)5.8 kW
Evaporating temperature-6°C
Panel thickness100 mm
Panel area (incl. 10%)118.8 m²
Recommended doorManual hinged insulated door
Recommended Refrigeration Unit
Bitzer MHT series · ANC04HF
1 × 8.62 kW = 8.62 kW total cooling capacity
- Evaporating temperature assumed as room temperature minus 8°C = -6°C.
- Capacity read from the MHT matrix at the -10°C column.
- Results are preliminary estimates; final selection requires engineering review of intake, door openings and ambient conditions.